Issue:
Soft Starters power factor correction capacitors (PFCC) recomcendations.
Product Line:
ATS46 and ATS48
Environment:
All series
Cause:
N/A
Resolution:
A capacitor placed on the output of a soft starter causes a short circuit across the SCR stacks upon startup, which may damage the SCRs. If PFCCs are required, the capacitors must be located on the line side of the ALTISTART Soft Start and should only be in the circuit while the motor is operating at full speed. Even when applied correctly to ensure that the ALTISTART starter can maintain synchronization within the line voltage, maximum correction for power factor should not exceed 95%.
See SquareD Bulletin No. 8638PD9603R1/98
Soft Starters power factor correction capacitors (PFCC) recomcendations.
Product Line:
ATS46 and ATS48
Environment:
All series
Cause:
N/A
Resolution:
A capacitor placed on the output of a soft starter causes a short circuit across the SCR stacks upon startup, which may damage the SCRs. If PFCCs are required, the capacitors must be located on the line side of the ALTISTART Soft Start and should only be in the circuit while the motor is operating at full speed. Even when applied correctly to ensure that the ALTISTART starter can maintain synchronization within the line voltage, maximum correction for power factor should not exceed 95%.
See SquareD Bulletin No. 8638PD9603R1/98
Diterbitkan untuk: Schneider Electric Indonesia




Perlu bantuan?
Pemilih produk
Temukan produk dan aksesoris yang tepat untuk aplikasi Anda secara cepat dan mudah.
Dapatkan Penawaran Harga
Silakan kirimkan pertanyaan terkait penjualan secara online dan pakar kami akan menghubungi Anda.
Tempat pembelian
Temukan distributor Schneider Electric terdekat di lokasi Anda dengan mudah.
Pusat Bantuan
Temukan sumber daya dukungan untuk seluruh kebutuhan Anda, di satu tempat.