How do you set the overload setting on the ATS48 soft starters?

Issue:
Programming Overload setting on the ATS48 soft starters

Product Line:
Altivar ATS48

Environment:
All

Cause:
Needs to set the overload settings.

Resolution:
Main menu arrow down to PRO enter
find tHP code enter
Your motor thermal protection options are going to be
Class 30
Class 25
Class 20 (Severe application)
Class 15
Class 10 (Standard application)
Class 10A
Sub Class 2
OFF: No Protection.

You can set your overload current set value in the SET menu
IN= set to the FLA or full load amps of your motor name plate.

Schneider Electric Indonesia

Lampiran
instruction bulletin enclosed ATS48.pdf [1.3 MB]

Perlu bantuan?

Perlu bantuan?

Pemilih produk

Pemilih produk

Temukan produk dan aksesoris yang tepat untuk aplikasi Anda secara cepat dan mudah.

Dapatkan Penawaran Harga

Dapatkan Penawaran Harga

Silakan kirimkan pertanyaan terkait penjualan secara online dan pakar kami akan menghubungi Anda.

Tempat pembelian

Tempat pembelian

Temukan distributor Schneider Electric terdekat di lokasi Anda dengan mudah.

Pusat Bantuan

Pusat Bantuan

Temukan sumber daya dukungan untuk seluruh kebutuhan Anda, di satu tempat.

  • Dokumentasi Produk
  • Unduhan Perangkat Lunak
  • Pemilih Produk
  • Penggantian dan Penggantian Produk
  • Pusat Bantuan dan Kontak
  • Temukan Kantor kami
  • Dapatkan penawaran harga
  • Tempat Pembelian
  • Komunitas Schneider Electric
  • Karier
  • Profil Perusahaan
  • Melaporkan pelanggaran
  • Aksesibilitas
  • Newsroom
  • Investor
  • EcoStruxure
  • Pencarian Pekerjaan
  • Blog
  • Kebijakan Privasi
  • Pemberitahuan Cookie
  • Ketentuan penggunaan
  • Change your cookie settings