Where do I enter the Engineering Client license for Power Monitoring Expert?
Issue:
How to properly license the Engineering Client in PME.

Product Line:
Power Monitoring Expert 7.2.x
Power Monitoring Expert 8.0

Environment:
Engineering Client installations
Power Monitoring Expert 7.2.x
Power Monitoring Expert 8.0

Cause:
After completing the Engineering Client installation in Power Monitoring Expert 7.2 (PME 7.2), some might wonder how to license the client install.

Resolution:
Unlike the primary server installation, the Engineering Client install does not include the Floating License Manager.
As a result, the activation ID should be entered on the primary server in the Floating License Manger and the client will point back to the primary server for its licensing.