Issue:
Needs to clear a fault code, on the ATS22 soft start.
Product Line:
Altistart 22
Environment:
All models
Cause:
The fault code must be cleared to make ATS22 functional.
Resolution:
After the condition that created the fault has been corrected, a fault reset can be accomplished several ways:
1) Remove control power from CL1-CL2. After the display has gone blank, apply control power.
2) On the integral or remote keypad, press the 3-key combination of ENT / UP arrow / DOWN arrow, simultaneously.
3) Wire a reset contact to logic input LI2 or LI3 and program it to rSt (remote reset). A momentary contact closure will reset.
4) Use Modbus command word 752 and write a 1 to bit 3
Note that several fault codes require method 1) above. These are InF, trAP, SCF.
Needs to clear a fault code, on the ATS22 soft start.
Product Line:
Altistart 22
Environment:
All models
Cause:
The fault code must be cleared to make ATS22 functional.
Resolution:
After the condition that created the fault has been corrected, a fault reset can be accomplished several ways:
1) Remove control power from CL1-CL2. After the display has gone blank, apply control power.
2) On the integral or remote keypad, press the 3-key combination of ENT / UP arrow / DOWN arrow, simultaneously.
3) Wire a reset contact to logic input LI2 or LI3 and program it to rSt (remote reset). A momentary contact closure will reset.
4) Use Modbus command word 752 and write a 1 to bit 3
Note that several fault codes require method 1) above. These are InF, trAP, SCF.
Diterbitkan untuk: Schneider Electric Indonesia
Perlu bantuan?
Pemilih produk
Temukan produk dan aksesoris yang tepat untuk aplikasi Anda secara cepat dan mudah.
Dapatkan Penawaran Harga
Silakan kirimkan pertanyaan terkait penjualan secara online dan pakar kami akan menghubungi Anda.
Tempat pembelian
Temukan distributor Schneider Electric terdekat di lokasi Anda dengan mudah.
Pusat Bantuan
Temukan sumber daya dukungan untuk seluruh kebutuhan Anda, di satu tempat.