How does one change the direction of the drive in a S-FLEX Drive without affecting bypass?

Issue:
S-FLEX Drive direction modification without affecting bypass

Product Line:
Altivar 212, ATV21, S-Flex, SFLEX

Environment:
All

Cause:
Wrong rotation in drive and correct rotation in bypass

Resolution:
With power disconnected from the unit, swap 2 of the leads leaving the T1, T2, and T3 terminals on the ATV212 or any 2 connecting to the input side of the drive output contactor (DOC).
Do NOT swap phases at the incoming circuit breaker or at the motor connections on the Overload Relay.
This will ensure that the drive's rotations is changed but bypass will stay the same.

Schneider Electric Indonesia

Jelajahi lebih lanjut
Rentang:
Jelajahi lebih lanjut
Rentang:

Perlu bantuan?

Perlu bantuan?

Pemilih produk

Pemilih produk

Temukan produk dan aksesoris yang tepat untuk aplikasi Anda secara cepat dan mudah.

Dapatkan Penawaran Harga

Dapatkan Penawaran Harga

Silakan kirimkan pertanyaan terkait penjualan secara online dan pakar kami akan menghubungi Anda.

Tempat pembelian

Tempat pembelian

Temukan distributor Schneider Electric terdekat di lokasi Anda dengan mudah.

Pusat Bantuan

Pusat Bantuan

Temukan sumber daya dukungan untuk seluruh kebutuhan Anda, di satu tempat.

  • Dokumentasi Produk
  • Unduhan Perangkat Lunak
  • Pemilih Produk
  • Penggantian dan Penggantian Produk
  • Pusat Bantuan dan Kontak
  • Temukan Kantor kami
  • Dapatkan penawaran harga
  • Tempat Pembelian
  • Komunitas Schneider Electric
  • Karier
  • Profil Perusahaan
  • Melaporkan pelanggaran
  • Aksesibilitas
  • Newsroom
  • Investor
  • EcoStruxure
  • Pencarian Pekerjaan
  • Blog
  • Kebijakan Privasi
  • Pemberitahuan Cookie
  • Ketentuan penggunaan
  • Change your cookie settings