PME - Too many registers exposed in Micrologic X driver to EWS
Issue

In PME8.2 and previous versions

1.    Too many registers exposed in Micrologic X driver (in this file only 66 measurements have been exposed similar to legacy Micrologic drivers)

2.    IONReferenceName and MeasurementName attributes and not aligned MM_MeasurementMap and PDM labels respectively

Environment

EWS service

Resolution

1.    Replace the Types.Measurements_MicrologicX file in C:\Program Files(x86)\Schneider Electric\Power Monitoring Expert\system\WebServices\Extensions

2.    Update the EWS server in Management console

Schneider Electric Indonesia

Lampiran
Types.Measurements_MicrologicX.XML.xml [113.57 KB]