Issues:
When configuring an ATV32 or ATV320: How do you set the drive to always stop by Freewheel and assign a Run Permissive?
Product Line:
ATV32 ATV320
Environment:
ALL
Cause:
Input to Stop
Resolution:
On the keypad of the drive, you will press the dial and go to the following:
Freewheel Stop Always: ConF > FULL > FUn- > Stt > Stt and set to nSt
Run permissive input: ConF > FULL > FUn- > Stt > nSt and assign that to a Logic/Digital Input.
**Keep in mind that Freewheel Stop [nSt] is an active Low input, so if you do not have the wiring in place, the drive will be locked in nSt state. Add a jumper from 24v to DIx/LIx assigned input until you have the actual contact installed.
When configuring an ATV32 or ATV320: How do you set the drive to always stop by Freewheel and assign a Run Permissive?
Product Line:
ATV32 ATV320
Environment:
ALL
Cause:
Input to Stop
Resolution:
On the keypad of the drive, you will press the dial and go to the following:
Freewheel Stop Always: ConF > FULL > FUn- > Stt > Stt and set to nSt
Run permissive input: ConF > FULL > FUn- > Stt > nSt and assign that to a Logic/Digital Input.
**Keep in mind that Freewheel Stop [nSt] is an active Low input, so if you do not have the wiring in place, the drive will be locked in nSt state. Add a jumper from 24v to DIx/LIx assigned input until you have the actual contact installed.
Diterbitkan untuk: Schneider Electric Indonesia




Perlu bantuan?
Pemilih produk
Temukan produk dan aksesoris yang tepat untuk aplikasi Anda secara cepat dan mudah.
Dapatkan Penawaran Harga
Silakan kirimkan pertanyaan terkait penjualan secara online dan pakar kami akan menghubungi Anda.
Tempat pembelian
Temukan distributor Schneider Electric terdekat di lokasi Anda dengan mudah.
Pusat Bantuan
Temukan sumber daya dukungan untuk seluruh kebutuhan Anda, di satu tempat.