Issue:
ATV320 with EtherNet/IP is not starting with assemblies 20/70.
Product Line:
ATV320
Environment:
Ethernet IP
Cause:
n/a
Resolution:
With assemblies 20/70, it's mandatory to respect dedicated drive configuration on : CD1, FR1, CHCF, CD2, FR2, CCS, RFC parameter
But in addition, it's mandatory to write via acyclic messaging the NetRef and NetCtrl parameters.
With Assemblies 20-70 «NetRef» and «NetCtrl» objects must be set by explicit messaging to control the drive by Network.
NetCtrl and NetRef are CIP object.
NetCtrl
This object defines if requests Run/Stop control come from local or from the network.
NetRef
This object defines if Requests torque or speed reference to be local or from the network.
Here with assemblies 20-70 its necessary there is no bit inside the assembly object so it’s necessary to send these 2 CIP objects by acyclic exchange
To activate the command by EtherNet/IP you need to write 1 in NetCtrl.
To activate the reference by EtherNet/IP you need to write 1 in NetRef.
You need to write these 2 CIP objects after:
- drive power on
- Disconnection of DeviceNet/Ethernet cable.
Note: The default setting (value 0) of NetCtrl and NetRef will applied each time you Power ON the drive or after DeviceNet/Ethernet cable disconnection.
Diterbitkan untuk: Schneider Electric Indonesia


Perlu bantuan?
Pemilih produk
Temukan produk dan aksesoris yang tepat untuk aplikasi Anda secara cepat dan mudah.
Dapatkan Penawaran Harga
Silakan kirimkan pertanyaan terkait penjualan secara online dan pakar kami akan menghubungi Anda.
Tempat pembelian
Temukan distributor Schneider Electric terdekat di lokasi Anda dengan mudah.
Pusat Bantuan
Temukan sumber daya dukungan untuk seluruh kebutuhan Anda, di satu tempat.