{}

Merek kami

Impact-Company-Logo-English Black-01-177x54

Selamat datang di Situs Web Schneider Electric

Selamat datang di situs web kami.

FAQ Pencarian

What is the difference in earth fault current internal measurement between 56517 and 56173?

56517 Earth-leakage relay RH197M - 0.03..30 A - 0..4.5 s - 240 V
-7 … 7 % is the accuracy of measurement between leakage current to earth detected by sensor and the current measured by the product.

56173 : Earth-leakage relay RH99M with manual reset - 0.03..30 A - 0..4.5 s - 240 V
80..100% is the detection range of a faulty current
For a particular Idn, the product will detect a fault if the current is between 80 and 100% of Idn

Schneider Electric Indonesia

Jelajahi lebih lanjut
Rentang:
VigiPacT
Jelajahi lebih lanjut
Rentang:
VigiPacT