How do I power cycle a Modicon M221 PLC with an SD Card inserted without cloning the application to the SD Card or requiring the run of a Script.cmd?
Environment
- If an inserted SD Card is does not contain at the root folder 'Script.cmd', the M221 will clone the application to the SD Card.
- If the inserted SD Card has 'Script.cmd', it will interrupt normal startup, execute the script.
- The Modicon M221 is of Functional Level 6.0 or higher a.k.a. a Boot loader version of 50 or higher - this can be checked in the system word %SW13
- The Modicon M221 has an SV number (on the sticker with the serial number) of 1.6 or higher (devices manufactured after May 2017).
- Put your SD Card in your PC card reader
- Open Windows File Explorer
- Right-click on the drive letter associated with the SD Card in File Explorer
- Choose "Properties"
- In the General Tab's first field presented at the top, set name of the SD Card to "DATA"
- Click OK
- Delete 'Script.cmd' from the root directory of the SD Card
- Eject the SD Card