PME 9.0 - New 3rd party device created with DTE does not work

Product Line
Power Monitoring Expert 9.0

Environment
DTE - Device Type Editor

Issue
The new devices created with DTE are not loading and you will see error messages in the System Log:

"Translator map file 'DEVICE_NAME.xml' not loaded due to previous error. Will retry."
"The attribute 'TimestampedByPlugin' on this element is not defined in the DTD/Schema." -
(or some other attribute as well)

Cause
The modbus-schema.xml file in the config/translator folder is an old version and does not contain the specific attribute referred by the error log.

Resolution
Replace the modbus-schema.xml file in config/translator with the one from system/translator folder or from a healthy PME system.

Schneider Electric Indonesia

Jelajahi lebih lanjut
Rentang:
Jelajahi lebih lanjut
Rentang:

Perlu bantuan?

Perlu bantuan?

Pemilih produk

Pemilih produk

Temukan produk dan aksesoris yang tepat untuk aplikasi Anda secara cepat dan mudah.

Dapatkan Penawaran Harga

Dapatkan Penawaran Harga

Silakan kirimkan pertanyaan terkait penjualan secara online dan pakar kami akan menghubungi Anda.

Tempat pembelian

Tempat pembelian

Temukan distributor Schneider Electric terdekat di lokasi Anda dengan mudah.

Pusat Bantuan

Pusat Bantuan

Temukan sumber daya dukungan untuk seluruh kebutuhan Anda, di satu tempat.

  • Dokumentasi Produk
  • Unduhan Perangkat Lunak
  • Pemilih Produk
  • Penggantian dan Penggantian Produk
  • Pusat Bantuan dan Kontak
  • Temukan Kantor kami
  • Dapatkan penawaran harga
  • Tempat Pembelian
  • Komunitas Schneider Electric
  • Karier
  • Profil Perusahaan
  • Melaporkan pelanggaran
  • Aksesibilitas
  • Newsroom
  • Investor
  • EcoStruxure
  • Pencarian Pekerjaan
  • Blog
  • Kebijakan Privasi
  • Pemberitahuan Cookie
  • Ketentuan penggunaan
  • Change your cookie settings