How do I prevent an ATV320 series drive from running in reverse?

Product Line:
ALTIVAR 320

Resolution:
Under CONF > FULL > I_O
rrs [REVERSE ASSIGN] set to "NO"

Under CONF > FULL > CTL
rin  [RV INHIBITION] set to "YES".

**NOTE:  Please note that if you have "RUN REVERSE" assigned to a logic input, setting RV INHIBITION to YES will not prevent the drive from running in reverse, if called to by the logic input.
RV Inhibition will prevent the motor from being run in reverse from the graphic display or when motor leads are not in the correct rotation.
Any speed reference, such as a PID reference, summing input, or any other speed reference that would normally cause the motor to run in reverse will now cause the motor to stop, when RV INHIBITION is set to YES.

Schneider Electric Indonesia

Jelajahi lebih lanjut
Produk:
Jelajahi lebih lanjut
Produk:

Perlu bantuan?

Perlu bantuan?

Pemilih produk

Pemilih produk

Temukan produk dan aksesoris yang tepat untuk aplikasi Anda secara cepat dan mudah.

Dapatkan Penawaran Harga

Dapatkan Penawaran Harga

Silakan kirimkan pertanyaan terkait penjualan secara online dan pakar kami akan menghubungi Anda.

Tempat pembelian

Tempat pembelian

Temukan distributor Schneider Electric terdekat di lokasi Anda dengan mudah.

Pusat Bantuan

Pusat Bantuan

Temukan sumber daya dukungan untuk seluruh kebutuhan Anda, di satu tempat.

  • Dokumentasi Produk
  • Unduhan Perangkat Lunak
  • Pemilih Produk
  • Penggantian dan Penggantian Produk
  • Pusat Bantuan dan Kontak
  • Temukan Kantor kami
  • Dapatkan penawaran harga
  • Tempat Pembelian
  • Komunitas Schneider Electric
  • Karier
  • Profil Perusahaan
  • Melaporkan pelanggaran
  • Aksesibilitas
  • Newsroom
  • Investor
  • EcoStruxure
  • Pencarian Pekerjaan
  • Blog
  • Kebijakan Privasi
  • Pemberitahuan Cookie
  • Ketentuan penggunaan
  • Change your cookie settings