BCM Summary button does not open branch circuit view on the HDPM6000 HMI
Issue
Selecting the "BCM Summary" button on the HDPM6000 HMI does not open the circuit view to view the individual branches.  The button appears to not be working.

Product line
HDPM6000
HDPM6000 HMI

Resolution
1. Open the HDPM6000 web page and login
2. Navigate to the "General Settings" tab
3. Set the "Phase summary" setting to "Circuits" or "Split Circuits"
4. Select the "Save circuit settings"

If "3 phase meter" is selected on the web page settings, the HMI will not show the branches when the "BCM Summary" button is pressed.

Webpage settings

Schneider Electric Indonesia

Jelajahi lebih lanjut
Rentang:
Produk:
Jelajahi lebih lanjut
Rentang:
Produk:

Perlu bantuan?

  • Pemilih produk

    Temukan produk dan aksesoris yang tepat untuk aplikasi Anda secara cepat dan mudah.

  • Dapatkan Penawaran Harga

    Silakan kirimkan pertanyaan terkait penjualan secara online dan pakar kami akan menghubungi Anda.

  • Tempat pembelian

    Temukan distributor Schneider Electric terdekat di lokasi Anda dengan mudah.

  • Pusat Bantuan

    Temukan sumber daya dukungan untuk seluruh kebutuhan Anda, di satu tempat.

  • Dokumentasi Produk
  • Unduhan Perangkat Lunak
  • Pemilih Produk
  • Penggantian dan Penggantian Produk
  • Pusat Bantuan dan Kontak
  • Temukan Kantor kami
  • Dapatkan penawaran harga
  • Tempat Pembelian
  • Karier
  • Profil Perusahaan
  • Melaporkan pelanggaran
  • Aksesibilitas
  • Newsroom
  • Investor
  • EcoStruxure
  • Pencarian Pekerjaan
  • Blog
  • Kebijakan Privasi
  • Pemberitahuan Cookie
  • Ketentuan penggunaan
  • Change your cookie settings