Issue:

SRTG 15 & 20kVA UPS requires a firmware update.

Product Line:

Smart-UPS models SRTG15KXLI and SRTG20KXLI

Environment:

  • Computer with Windows 7 or Windows 10 operating system
  • The USB A to USB B type communication cable supplied with the UPS
  • "UPS-UpdateToolInstaller.zip" file - available at the end of this document
  • "15-20k V1.19 20220909.zip" Firmware File - available at the end of this document


Resolution:

NOTE: The UPS system is expected to power down during the firmware upgrade. It is recommended to turn off the load connected to the UPS before starting the firmware upgrade.

Preparation:

  1. Connect the USB A to USB B type communication cable supplied with the UPS cable between the UPS and computer.
    • 1
  2. Download the "UPS-UpdateToolInstaller.zip" and "15-20k V1.19 20220909.zip" files attached at the end of this document.
  3. Extract the "UPS-UpdateToolInstaller.zip" file.


Installing the Update Tool:

Double click the "UPS-UpdateToolInstaller.exe" file to start installing the update tool.

  1. Select OK.
    • 2
  2. Select Next.
    • 3
  3. Select Install.
    • 4
  4. Ensure that the "Launch UPS-UpdateTool" option is selected, and then select Finish. This will launch the update tool.
    • 5


Updating the UPS Firmware:

  1. Select the language: English.
    • 6
  2. Select the appropriate port number where the USB cable is connected to the computer.
    • 7
  3. Press "select" and browse to the location where the "15-20k V1.19 20220909.zip" file was downloaded in Preparation Step 2.
    • 8
    • 9
  4. Ensure both check boxes are ticked:
    • 10
  5. Select Updating:
    • 11
  6. The update may take 15-20 minutes. Once the update is completed, the update tool can be closed:
    • 12

Verifying the firmware version

Use the UPS front panel to navigate to the following menus.

  1. Press the OK key to enter the Main Menu, press the ▼ key to select Configuration and press the OK key to enter the submenu.
    • 13
  2. Press the ▼ key to select Display, and click OK to enter the submenu.
    • 14
  3. Press the ▼ key to select the Menu Type, and click OK to enter the menu type selection screen.
    • 15
  4. Press ▼ key to select Advanced, and press OK to confirm.
    • 16
  5. Press ESC key until you return to the Main Menu.
  6. In the Main Menu, press the ▼ key to select About, click OK to enter the submenu.
    • 17
  7. Select UPS and click OK to enter the submenu.
    • ​​​​​​​18
  8. Press the ▼ key to view firmware component versions.
    • ​​​​​​​​​​​​​​19 ​​​​​​​

Schneider Electric Indonesia

Lampiran
UPS-UpdateToolInstaller.zip [10.77 MB]
15-20k V1.19 20220909.zip [301.17 KB]
Jelajahi lebih lanjut
Produk:
Jelajahi lebih lanjut
Produk:

Perlu bantuan?

Perlu bantuan?

Pemilih produk

Pemilih produk

Temukan produk dan aksesoris yang tepat untuk aplikasi Anda secara cepat dan mudah.

Dapatkan Penawaran Harga

Dapatkan Penawaran Harga

Silakan kirimkan pertanyaan terkait penjualan secara online dan pakar kami akan menghubungi Anda.

Tempat pembelian

Tempat pembelian

Temukan distributor Schneider Electric terdekat di lokasi Anda dengan mudah.

Pusat Bantuan

Pusat Bantuan

Temukan sumber daya dukungan untuk seluruh kebutuhan Anda, di satu tempat.

  • Dokumentasi Produk
  • Unduhan Perangkat Lunak
  • Pemilih Produk
  • Penggantian dan Penggantian Produk
  • Pusat Bantuan dan Kontak
  • Temukan Kantor kami
  • Dapatkan penawaran harga
  • Tempat Pembelian
  • Komunitas Schneider Electric
  • Karier
  • Profil Perusahaan
  • Melaporkan pelanggaran
  • Aksesibilitas
  • Newsroom
  • Investor
  • EcoStruxure
  • Pencarian Pekerjaan
  • Blog
  • Kebijakan Privasi
  • Pemberitahuan Cookie
  • Ketentuan penggunaan
  • Change your cookie settings