Can we adjust number of communication requests processed per master task cycle in Modicon Quantum
For modicon Quantum you can configure the server resources using %SW90 system word.  This word is used to set a maximum number of requests (all protocols included: UNI-TE, Modbus, etc.) which can be processed by the server of the PLC per master task cycle. (Requests sent by the PLC as client are not concerned.) This number of requests must be between a minimum and a maximum (defined as N+4) depending on the model. The number of requests to be processed per cycle should take into account requests from all communication ports (having access to the server). This means that requests from other clients than
communication EFs, like IO Scanner, connected HMI and so on, should also be taken into account. For Quantum range:

140 CPU 31••/43••/53••/: N = 10 (minimum 5, maximum 10 + 4 = 14),
140 CPU 6••: N = 20 (minimum 5, maximum 20 + 4 = 24)

Schneider Electric India

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Contact support - +1800-103-0011
  • Price List
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings