{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
How can we help you today?
What is the purpose of Reset button on M340 Power Supply Module.
The power supply module has a Reset button on its front panel which, when pressed, triggers an initialization sequence of the modules on the rack that it supplies.

Sequence Generated by Pressing the Reset Button:
When the Reset button is pressed, the following events occur:
  • The INIT_BAC_N signal is enabled and forces all the modules on the rack to reset to 0.
  • The RESET_BUTTON signal is enabled and forces the processor to reset to 0, which in turn leads to the following events:
-  The ALARM relay is forced to open state.
-  The power supply OK LED is switched off.

Pressing/releasing the Reset button triggers a cold start. The connectors around the Reset button are energized.

Schneider Electric India

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: