Whenever a command is issued a code appears in the event log for each control operation. These are the following codes and the reasons indicating the status of each control operation.
Main switchgear control failure variable | |
Value (potential issue code) | Description |
0 | Command completed successfully |
1 | Local command blocked because switch position is intermediate or unknown |
2 | Local command blocked because switch position is already in correct state |
3 | Local command canceled by user |
4 | Switch position did not change within configured maximum operation time |
5 | Command blocked by Head Unit interlocks, e.g. potential motor supply issue or battery low |
6 | Command did not execute due to timeout waiting for enable from Head Unit |
7 | Local command blocked because disabled by configuration |
8 | Local command blocked because local/remote status is unknown |
9 | Local command blocked because local/remote status is remote |
10 | Local command blocked because automation is on |
11 | Remote command blocked because automation is on |
12 | Sectionalizer command blocked because automation is off |
13 | Sectionalizer command blocked because local/remote status is unknown |
14 | Sectionalizer command blocked because local/remote status is local |
15 | Unexpected command source (firmware potential issue) |
16 | Remote command blocked because requested position is not a valid value |
17 | Command blocked because a command is already in progress for this module |
18 | Command blocked because the power shutdown signal is active |
19 | Command blocked because a command is already in progress for another module |
20 | Command blocked because measured switch position is intermediate or unknown |
21 | Command blocked because measured switch position is the same as the requested position |
22 | Command blocked because ground (earth) switch position is not open |
23 | Open command blocked because external input is false |
24 | Open command blocked because external input is true |
25 | Close command blocked because external input is false |
26 | Close command blocked because external input is true |
27 | Commands blocked because module behaviour mode is off |
28 | Command blocked because switch controller is in local mode |
29 | Command blocked because switch controller local/remote input is undefined |
30 | Command blocked because protection trip lockout is active |
31 | Command blocked because the OPEN/CLOSE command is in progress |
32 | Command blocked because a self-test is in progress |
Released for: Schneider Electric India
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales enquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.