Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
How Line Voltage (ULN) is Calculated in ATV320 Drive
Input voltage of the drive ULN is calculated according to the DC bus voltage.
The accuracy depends on the type of application (motor mode or generator mode, with or without load). According to the situation:
- Optimal accuracy is less than 5%
- IGBT bridge locked (without motor current)
- Run without load
- When load apply on motor accuracy is around 10-15%.
- In generator mode: Information is not significant because DC bus value increase.

This value display come from the DC bus: ULN = Vbus (average value) / square root of 2

Schneider Electric India

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Contact support - +1800-103-0011
  • Price List
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings