How to remove the LED Alarm in MiCOM Px3x
After the reboot of the device, the ALARM LED is ‘on’ due to a deliberate distortion of the parameter checksum which initializes the desired cold restart automatically.

Please read out the corresponding entries in the monitoring signal memory
(‘MiCOM Px3x / Operation / Operating data rec. / MT_RC / Mon. signal record.’):
Use the right arrow button to read all the entries.

In order to switch off the ALARM LED please clear the monitoring signal memory
(‘MiCOM Px3x / Operation / Control and Testing / MT_RC / Reset recording’):
Oper/CrtlTest/MT_RC
Reset recording
2

Please enter the input mode, change the value to ‘execute’:
Oper/CrtlTest/MT_RC
Reset recording
2
Execute

and press the ENTER key. The number of entries in the monitoring signal memory will be ‘0’ now and the ALARM LED will go ‘off’:
Oper/CrtlTest/MT_RC
Reset recording
0

Schneider Electric India

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Contact support - +1800-103-0011
  • Price List
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings