The VW3A7702 is provided with PA+ / PB terminals, T1 and T2 terminals.
The T1 & T2 terminals are "NC" contacts of inbuilt thermistor relay. This "NC" contact should be connected in series to the braking resistor.
The connection should be
PA (drive) to PA (resistor) - Connection 1
PB (drive) to T1 (resistor) - Connection 2
T2 (resistor) to PB(resistor) - Connection 3
Find below attached instruction sheet for reference.
The T1 & T2 terminals are "NC" contacts of inbuilt thermistor relay. This "NC" contact should be connected in series to the braking resistor.
The connection should be
PA (drive) to PA (resistor) - Connection 1
PB (drive) to T1 (resistor) - Connection 2
T2 (resistor) to PB(resistor) - Connection 3
Find below attached instruction sheet for reference.