Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
Testing and tripping of AC/DC MCB.
The test procedure for MCBs thermal tripping verification is the same in AC and DC with normally no difference of product behaviour.
The test procedure is: Int=1.13.In no tripping (3600s for 6-10A starting from cold) and It=1.45.In tripping (≤3600s immediately following Int) according to 9.10.2.1 of IEC 60898-1 std.

Confirm that the current pass through all poles with the reference conditions as per the IEC standard operating at the reference calibration temperature of 30 °C 0/+5°C.
Confirm that the cross-section of conductor cable is in accordance with Tb.10 with 1m of length for cross-sections up to and including 10 mm².

Schneider Electric India

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Contact support - +1800-103-0011
  • Price List
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings