After logging to the MP series controller using eCommissioning Tool, it is not possible to change anything and all settings appeared to be read-only.
It indicates that currently hosted under another BMS Server. Follow below steps:
  • Login to the EBO (> v2.0).
  • Delete the SmartX IP controller from IP Network.
  • Click AS-P and go to Device Discovery.
  • Select BACnet devices from the drop-down list.
  • SmartX IP Controller will appear in device discovery.
  • Right click the controller and select 'clear host information'.
  • Login to the SmartX eCommissioning Tool. Now all the parameters can be accessed and modified.

Schneider Electric India

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:

Need help?

  • Product Selector

    Quickly and easily find the right products and accessories for your applications.

  • Get a Quote

    Start your sales enquiry online and an expert will connect with you.

  • Where to buy?

    Easily find the nearest Schneider Electric distributor in your location.

  • Help Centre

    Find support resources for all your needs, in one place.

  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Contact support - +1800-103-0011
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings