After logging to the MP series controller using eCommissioning Tool, it is not possible to change anything and all settings appeared to be read-only.
It indicates that currently hosted under another BMS Server. Follow below steps:
  • Login to the EBO (> v2.0).
  • Delete the SmartX IP controller from IP Network.
  • Click AS-P and go to Device Discovery.
  • Select BACnet devices from the drop-down list.
  • SmartX IP Controller will appear in device discovery.
  • Right click the controller and select 'clear host information'.
  • Login to the SmartX eCommissioning Tool. Now all the parameters can be accessed and modified.