For Unity CPUs (standard CPUs and Safety CPUs), the following system words that can be referred are from %SW535 to %SW640 for RIO Network Diagnosis.
To detect global communication:
 To detect global communication:
1.) %SW535 (RIO error on start-up), 
2.) %SW536, %SW537, %SW538 (Communication status on cable A),
 2.) %SW536, %SW537, %SW538 (Communication status on cable A),
3.) %SW539, %SW540, %SW541 (Communication status on cable B),
 4.) %SW542, %SW543, %SW544 (Global communication status)
  To detect errors coming from the drops:
 1.) %SW545 to 640 (Status of decentralized stations) for communication error bits: 
 2.) %SW545 to %SW547 are dedicated to the local station
 3.) %SW548 to %SW550 are dedicated to the drop 2
 4.) %SW551 to %SW553 are dedicated to the drop 3
 5.) %SW553 to %SW556 are dedicated to the drop 4
 6.) and so on....