For the ATV71 or ATV61 using serial communications, how are the units determined for energy consumption or operating time?
Issue:
What are the type of units for energy consumption or operating time on AT61/71 when using serial communications?
Product Line:
Altivar 61, Altivar 71
Environment:
Serial communications
Cause:
Clarification
Resolution:
The UNT is of type, word and is a Read Only register in the ATV71 (addr 3234).
It is used internally to determine the proper units to display for time and energy readings.
See the description for the following parameters to determine which bits of word 3234 are used for the corresponding values.
The Pth, Aph, Rth, Rthi are displayed on the ATV71 with the proper units shown s, m, hr. So, this UNT reading was left out of the communication parameter manual.
**See the Communication parameters manual or spreadsheet for further information.
What are the type of units for energy consumption or operating time on AT61/71 when using serial communications?
Product Line:
Altivar 61, Altivar 71
Environment:
Serial communications
Cause:
Clarification
Resolution:
The UNT is of type, word and is a Read Only register in the ATV71 (addr 3234).
It is used internally to determine the proper units to display for time and energy readings.
See the description for the following parameters to determine which bits of word 3234 are used for the corresponding values.
The Pth, Aph, Rth, Rthi are displayed on the ATV71 with the proper units shown s, m, hr. So, this UNT reading was left out of the communication parameter manual.
**See the Communication parameters manual or spreadsheet for further information.
게시 대상: 슈나이더 일렉트릭 Korea




도움이 필요하신가요?
제품 선택기
애플리케이션에 적합한 제품과 액세서리를 빠르고 쉽게 찾을 수 있습니다.
견적 받기
영업 관련하여 온라인으로 문의하시면 전문가가 연락드립니다.
구매처
해당 지역의 가장 가까운 슈나이더 일렉트릭 대리점을 쉽게 찾을 수 있습니다.
지원 센터
한 곳에서 모든 요구 사항에 대한 지원 리소스를 찾아보십시오.