브랜드

슈나이더 일렉트릭 코리아 웹사이트에 방문해 주셔서 감사합니다.

슈나이더 일렉트릭 코리아 웹사이트 방문자 분들 모두 환영합니다.
		
오늘 무엇을 도와드릴까요?
Data Center Expert | How do I upgrade my software version?
Issue:
Process for upgrading StruxureWare Data Center Expert.

Product Line
StruxureWare Data Center Expert (DCE)
- Basic Appliance (AP9465)
- Standard Appliance (AP9470)
- Enterprise Appliance (AP9475)
- Virtual Appliance (AP94VMACT)

Environment:
StruxureWare Data Center Expert (all versions)

Resolution:

You must have a valid currently active software support contract to receive upgrade files.

See FA372574 for instructions on preparing for the upgrade, which include:
  • Software Support verification through technical support to receive upgrade files.
  • Verifying the Checksum (integrity) of upgrade files.
  • Virtual Appliance hard disk requirements.
  • Creating a Backup before upgrading.



1) Download the upgrade.zip file and verify the checksum.

2) Extract the downloaded upgrade.zip file. As of 7.9.3 going forward, extracting the contents of the zip file is not required.

3) Login to the DCE Desktop Client, select the Updates Menu, and then select Apply Server Update.

4) Select Import and navigate to the extracted upgrade file. (or zip file if 7.9.3 or higher.)  Select Open.

5) Select Install Update to start upgrading the server.

6) Monitor the progress of the update on the web interface of DCE.
NOTE: Upgrades usually take an hour or less to complete, but for certain upgrades it may take significantly longer depending on the number of devices and amount of historical data.

7) When prompted for login on the web interface, log in and install the new desktop client.  Instructions for downloading and installing the desktop client can be found in knowledge base FA272226.

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings