브랜드

슈나이더 일렉트릭 코리아 웹사이트에 방문해 주셔서 감사합니다.

슈나이더 일렉트릭 코리아 웹사이트 방문자 분들 모두 환영합니다.
		
오늘 무엇을 도와드릴까요?
How can running frequencies be skipped in an ATV61/ATV71 ?

Article available in these languages: 스페인어

Issue:
Skipping output frequencies in an ATV61/ATV71

Product Line:
Altivar ATV61 and ATV71

Environment:
All

Cause:
Motor is making a noise when running within a certain speed range.

Resolution:
In menu 1.3 Settings, adjust the following parameters:
Skip Freq (JPF) = midpoint of the skipped range
Skip Freq Hysteresis (JFH) = number of frequencies to be skipped above and below the midpoint

This function prevents the VFD from outputting undesirable motor speeds.  It is typically used to skip over a resonance frequency range that can result in pronounced or excessive motor noise.

The skip frequency range is (JPF – JFH) to (JPF + JFH).  The JFH hysteresis is common to all 3 skip frequency functions (JPF, JF2 and JF3).

Example :
Skip Freq = 30Hz
Skip Freq Hysteresis = 2
The skipped range will include 2Hz below and 2Hz above the 30Hz Skip Freq.
The total skipped range is 28Hz - 32Hz.

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings