브랜드

Impact-Company-Logo-English Black-01-177x54

슈나이더 일렉트릭 코리아 웹사이트에 방문해 주셔서 감사합니다.

슈나이더 일렉트릭 코리아 웹사이트 방문자 분들 모두 환영합니다.
		
오늘 무엇을 도와드릴까요?
What is the UCF trip code on the ATS22? How is it triggered?
Issue:
Needs to understand the UCF (Motor Underload or Undercurrent Fault)

Product Line:
ATS22

Environment:
All models, all part numbers.

Cause:
N/A

Resolution:
This is a motor underload (undercurrent) condition based on the setting of parameters UId and UIt in the Protections menu, PrO.
UId is the undercurrent threshold as a % of parameter In, motor rated current.  It can be set to oFF to disable the feature.
UIt is the undercurrent time delay.
In a run state, if the motor current remains below the UId threshold for the UIt time period, the ATS22 will trip on UCF.
UCF detection is based on average amps.
Average current has to be nonstop below the UId level (if average exceeds (even for just a moment) UId,level, the UIt time counter re-starts from 0).
Note: The customer must also consider the current measurement accuracy (about 5%).

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings