브랜드

슈나이더 일렉트릭 코리아 웹사이트에 방문해 주셔서 감사합니다.

슈나이더 일렉트릭 코리아 웹사이트 방문자 분들 모두 환영합니다.
		
오늘 무엇을 도와드릴까요?
Video: How is basic programming performed on the ATS22 Soft Starter?

Article available in these languages: 스페인어

Issue:
How do I perform basic programming on the ATS22?

Product Line:
Altistart 22 Soft Start

Environment:
All models and serial numbers

Resolution:

Basic Programming:

Conf Menu
Uln = line voltage
In= motor rated current (motor FLA)
LAC= Advanced mode to access other menus

Set Menu
t90= Initial voltage
ILt= current limit (max current the motor will be allowed to pull)
ACC= Acceleration time (user preference per application requirements)
DEC= Deceleration time (user preference per application requirements)
tHP= Motor thermal protection (10,20,30)  Note: To activate tHP, set ItH to ErUn or On

Pro Menu
ItH= Overload protection (oFF / ErUn / On)

The following video walks the user through basic configuration of the ATS22:



The basic programming parameters to set up an ATS22 Soft Start can also be found in the User Manual.
https://www.se.com/us/en/download/document/BBV51330/

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings