브랜드

슈나이더 일렉트릭 코리아 웹사이트에 방문해 주셔서 감사합니다.

슈나이더 일렉트릭 코리아 웹사이트 방문자 분들 모두 환영합니다.
		
오늘 무엇을 도와드릴까요?
Altivar 61/71: How to perform a voltage balance test
Issue:
ATV61/71 - voltage balance test

Product line:
Altivar 61
Altivar 71

Environment:
All models, all serial numbers

Cause:
Test to determine if the drive output voltage is balanced.

Resolution:
This is a voltage balance test.  It tests the drive output voltage for balanced voltage between the three phases.  If the output voltage is evenly balanced the drive is deemed to be good and the problem is in the motor or motor wiring.

1  You must disconnect the motor from the drive.

2.  Set parameter "Output Phase Loss" to no.

a. Enter the "Drive" menu

b. Scroll down to menu 1.8 Fault Management and press enter

c. Scroll down the "OUTPUT PHASE LOSS" and press enter

d. Press enter again on "Output Phase Loss"

e. Assign to "No" (you will see the checkmark to the right).

f.  Press "ESC" out to "Drive Menu"

3.  Make sure the drive is in V/F 2pts mode.
a.  Menu 1.4 Motor control -

b.  change [motor control type] to VF2pts.

4. Run the drive at  low (20 Hz), medium (40 Hz) and high (60 Hz) speeds.  With a True RMS volt meter measure the voltage between all three phases (T1 to T2, T1 to T3 and T2 to T3) at each speed.  All measurements should be balanced within a volt or two for a given speed.

If voltages are balanced, the IGBT's in the drive are operating properly.

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings