오늘 무엇을 도와드릴까요?

Why has PowerChute Software lost communication with UPS after communication cable has been unattached and reattached?

Issue:
After detaching the communication cable and then reattaching the communication cable, PowerChute Software does not reestablish communications with the UPS.

Product:
PowerChute Serial Shutdown
PowerChute Business Edition

Environment:
All supported OS communicating with UPS via USB or Serial to Smart-UPS

NOTE: PowerChute Business Edition versions up to 10.0.5 are incompatible with Back-UPS.

Cause:
The communications cable was unattached while the PowerChute service or daemon was running on the OS.

Solution:

1 – Stop the PowerChute service or daemon before detaching and reattaching the communications cable.

2 – If the cable is unattached while the server or daemon is running, you can re-establish communications by

a: Stopping and restarting the server or daemon.

b: If step a does not resolve the issue, stop the service or daemon again, reattach the cable, and then brain-dead the UPS.  See Video: How to perform a cold start and brain dead on Smart-UPS for instructions on how to brain-dead a Smart-UPS.

c: For other lost communication troubleshooting steps, see Schneider Electric Video: Troubleshooting no communication between UPS and PowerChute Business Edition or PowerChute Serial Shutdown

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings