What causes an OPF1 fault on the ATV61 or ATV71 drives?
Issue:
OPF1 on ATV61/ATV71 drives.
Product Line:
Altivar ATV61 and ATV71
Environment:
All ATV61 and ATV71 drives
Cause:
1 phase loss between the drive and motor.
Resolution:
This fault is triggered when the drive detects one of the motor phases has been lost (or has very low current) for more than 500 msec.
Troubleshooting steps:
- Check all connections between the drive and the motor. Re-seat connections and check for torque.
- Using clamp-on measure current on each motor lead to see if you have low current on one or more phases.
- Using a 1000 V Megger, test the motor and leads.
- For testing, set Motor Control Type = VF2pts, Output Phase Loss = No, disconnect the motor leads from the drive, run the drive at 20Hz, 40Hz, and 60Hz, and measure output voltage phase to phase at each speed. You want the voltages balanced and correct for the speed you're running the drive. Be aware that your meter may read higher output voltage than you might expect (for example, you may measure over 500V at 60Hz) if your meter doesn't have a PWM filter. This is because you're measuring a PWM (Pulse Width Modulated) waveform and not true AC. Be sure to turn OPL detection back on after testing.
- Go to 1.8 menu: Scroll down to Output Phase loss- Output time detect- set to 5 secs. Power cycle the drive and then try to run again.
게시 대상: 슈나이더 일렉트릭 Korea
도움이 필요하신가요?
제품 선택기
애플리케이션에 적합한 제품과 액세서리를 빠르고 쉽게 찾을 수 있습니다.
견적 받기
영업 관련하여 온라인으로 문의하시면 전문가가 연락드립니다.
구매처
해당 지역의 가장 가까운 슈나이더 일렉트릭 대리점을 쉽게 찾을 수 있습니다.
지원 센터
한 곳에서 모든 요구 사항에 대한 지원 리소스를 찾아보십시오.