Power cycling the STBNIP2212 causes the island RDY lights to blink.

Issue
Power cycling the STBNIP2212 causes the island RDY lights to blink.

Product Line
Advantys Ethernet NIM p/n STBNIP2212

Environment
Windows 7

Resolution
The problem could occur if the NIM has a SIM card inserted and the SIM card does not have a
configuration on it. If the SIM has a configuration in it, it could be corrupted.

Under normal conditions, when the Advantys NIM is powered cycled with a SIM inserted in it, the
NIM is designed to boot up using valid configuration on the SIM card. If it does not find a valid
configuration on the SIM card, the island will go into fallback mode. When the island is in fallback
mode, the RDY lights will blink and the island inputs and outputs will go to zero or it's configured
fallback value.

To resolve the problem:

Check to see if there is a valid configuration on the SIM card. If there is none, use the following steps to
configure it.

  • Remove the SIM card.
  • Power up the island.
  • Start the Advantys Configuration Software.
  • Create a configuration and download it to the NIM.
  • Insert the SIM card into the NIM while it is powred up.
  • Click on Online\Connect to connect to the NIM.
  • Click on 'Online\Store to SIM card'
  • Store the configuration to the SIM.
  • Disconnect Advantys Configuration Software from the NIM.
  • Power cycle the NIM.



슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군

도움이 필요하신가요?

도움이 필요하신가요?

제품 선택기

제품 선택기

애플리케이션에 적합한 제품과 액세서리를 빠르고 쉽게 찾을 수 있습니다.

견적 받기

견적 받기

영업 관련하여 온라인으로 문의하시면 전문가가 연락드립니다.

구매처

구매처

해당 지역의 가장 가까운 슈나이더 일렉트릭 대리점을 쉽게 찾을 수 있습니다.

지원 센터

지원 센터

한 곳에서 모든 요구 사항에 대한 지원 리소스를 찾아보십시오.

  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings