What is the maximum number of client and server connections on an ETY4103/5103
Issue
What is the maximum number of client and server connections on an ETY4103/5103
Product LIne
TSXETY4103 and TSXETY5103
Environment
Windows 7
Resolution
The following applies to exec fimrware version 4.xx and higher of the 'TSXETY4103' and 'TSXETY5103':
- The ETY4103/ETY5103 has a limit ot 64 connections.
- The connections can be a combination of both client and server. (i.e., 16 clients and 48 server, etc.) .
- 16 of the connections are dedicated for the client.
- There is a limit of 64 connections regardless of the type of connections (i.e., HTTP, TCP, etc.).
- When counting client connections, consideration must also be given for other client connections
- There can be up to 64 connections open but, only 16 simultaneous client connections can be running
connection will be reserved for listening.