Can I use a HART enabled device with the M340 analog input module?

Issue:

Can I use a HART enabled device with the M340 analog input module?

Product Line:

M340 Analog Input Module, Control Expert

Resolution:
Yes, the BMXAMI0800 and BMXAMI0810 modules will support analog signals with HART protocol.

If HART information is part of the signal to be measured, a Telefast interface
ABE7CPA31E has to be used to filter this information which would disrupt the analog value.

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.