In a Quantum RIO Network, using 140CRP93100 module, PV<08 with 140CRA93X00 modules with PV=09 and DOM<1102 is causing an increase of the RIO Communication Error .

Release Notice

This Resolution follows the 204138 one, some modification and add of binary Q201.bin file has been released.
05/01/2012 : add on of the compatiblity rules

Goals and Symptoms

In a Quantum RIO Network, using 140CRP93100 module, PV<08 (non RoHS design) with 140CRA93X00 modules, PV>=09 (RoHS design), is causing an increase of the RIO Communication Error counters (global communication error words: %SW542 to %SW544, and status of the decentralized stations: %SW548 to %SW640).

Facts and Changes

Cause :
Root cause of the issue is a bad synchronization (in reception) of one component mounted on 140CRA93X00 RoHS PRODUCTS when non RoHS 140CRP93100 is sending some initializing frames.
Only 140CRP93100 non RoHS product can send this kind of frames.

Causes and Fixes

Block *:Causes and Fixes
Workaround:
either change the 140CRP93100, PV< 08 (non RoHS design), for a new 140CRP93100, PV>=08 (RoHS design).
or upgrade the FW of the 140CRP93100 PV<08 using the following attached file :Qcrpv201.bin

Caution: Qcrpv201.bin file is:
  • only for a workaround, this will not be delivered in a product from =S=. So this will not delivered in Planet .
  • doesn't work with S800 series .

Fix:
So far the fix is included in the produced versions of the 140CRA93100 and 140CRA93200 with the following tracability indexes:
PV >= 9
SV >= 2.0
RL >= 01 (printed on the top of the housing)
DOM >= 1102.

CRP/CRA/S800 .... Compatiblity rules is provided below .
As soon as a new module will be implemented in a PLC configuration, please refer to this excel file to see if the compatibilty is supported, in case of problem contact the support with a description of the problem and the list of the PV and SV of the modules .
Single or HSBY configuration is described.

Attachements

Exec v2.01 (qcrp201.bin) 12/09/10 This version provides a workaround regarding the problem of mixed CRA/CRP : CRP non RoHS and CRA RoHS.

(Removed File URL: 204828_12FE/QCRPV201.BIN)(Removed Image URL: /PubResEXPORT.nsf/2b87ee90be777fc085257c28006ee4ef/216bfc64a56bbaafc1257988002c0d1e/fl_block_5/0.646?OpenElement&FieldElemFormat=gif)

Compatiblity rules: (Removed File URL: 204828_12FE/CRP-CRA_compatibilty.xls)(Removed Image URL: /PubResEXPORT.nsf/2b87ee90be777fc085257c28006ee4ef/216bfc64a56bbaafc1257988002c0d1e/fl_block_5/0.1248?OpenElement&FieldElemFormat=gif)


Legacy KB System (APS) Data: RESL204828 V3.0, Originally authored by ErBe on 03/16/2011, Last Edited by ErBe on 01/17/2012
Related ranges: Modicon Quantum

슈나이더 일렉트릭 Korea

첨부 파일
CRP-CRA_compatibilty.xls [29 KB]
QCRPV201.BIN.bin [248 KB]
자세히 알아보기
제품군
자세히 알아보기
제품군

도움이 필요하신가요?

도움이 필요하신가요?

제품 선택기

제품 선택기

애플리케이션에 적합한 제품과 액세서리를 빠르고 쉽게 찾을 수 있습니다.

견적 받기

견적 받기

영업 관련하여 온라인으로 문의하시면 전문가가 연락드립니다.

구매처

구매처

해당 지역의 가장 가까운 슈나이더 일렉트릭 대리점을 쉽게 찾을 수 있습니다.

지원 센터

지원 센터

한 곳에서 모든 요구 사항에 대한 지원 리소스를 찾아보십시오.

  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings