브랜드

슈나이더 일렉트릭 코리아 웹사이트에 방문해 주셔서 감사합니다.

슈나이더 일렉트릭 코리아 웹사이트 방문자 분들 모두 환영합니다.
		
오늘 무엇을 도와드릴까요?
In Vijeo Designer, what changes in the application will require to delete Preserve Runtime Data on download?

    • Changes to recipe or security data while editing the project may cause incompatibility with the run-time data or result in data that cannot be preserved. For example:
        • If any variable is changed while editing the project, even a variable that is not related to the recipes, all recipe data cannot be preserved.
        • If a single recipe is changed (i.e., a change to a recipe's name, ingredient list, or recipe value), all recipe data cannot be preserved.
        • If a recipe group is added to or deleted from a recipe group, all recipe data cannot be preserved.
        • If a recipe group is added, deleted, or changed, all recipe data cannot be preserved.
        • If security data is changed (i.e., a user group is modified), the existing security data on runtime can be preserved but the modified security data will not be downloaded.

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings