How do you import the tags from the RSLogix5000 L5K file in Vijeo Designer using the Link Variables feature?

Issue
How do you import the tags from the RSLogix5000 L5K file in Vijeo Designer using the Link Variables feature?
Product Line
Vijeo Designer

Environment
Configuration software in Windows PC

Resolution
From RSLogix5000, you will need to re-save the project file as a L5K file format. By going to the File menu and select Save As..
image

From the SaveAs window, create a path and file name of where you want to save the file. Make sure you select L5K as the file type then select Save
image

In Vijeo Designer, create the Rockwell Ethernet IP native driver. In this example, I am using the CompactLogix PLC. But you need to select the controller you are using.
iamge
image

Input the IP address
image

<right-click> on the Variables node and select Link Variables.
image

From the Link Variables window, locate the path of the L5K file that you have saved. Select File of Type as Rockwell L5K Files and EQUIPMENT name of the EIP driver you have created then select OK.
image

From the New Variables from EQUIPMENT, select the tags you want to import into Vijeo Designer. Under the When adding variables: option, select how you want to save the tag names and select add.
image

Once the link variables are complete, you will see all of the variables you have imported in the variable editor window.
image

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)


슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings