브랜드

슈나이더 일렉트릭 코리아 웹사이트에 방문해 주셔서 감사합니다.

슈나이더 일렉트릭 코리아 웹사이트 방문자 분들 모두 환영합니다.
		
오늘 무엇을 도와드릴까요?
'The core database has not been found or it is an incompatible version' error message

Issue
'The core database has not been found or it is an incompatible version' error message

Product Line
Advantys

Environment
Windows 7

Resolution
This error message appears when the Advantys Configuration Software is opened.

This error will occur if the pathname in the registry key does not match the actual database path that
the workspace is using.

To verify the pathname for the database folder:

  • Click on Start\Run
  • Type in 'regedt32' and hit the ENTER key to bring up the Registry Editor.
  • Open the HKEY_LOCAL_MACHINE folder.
  • Double click on the Registry key named Schneider Electric.
  • Double click on the Registry key named Advantys\Settings.
  • Double click on the Registry key named Settings.
  • Locate the key data in the right window pane and compare it against the actual folder pathname. (i.e., The key
data is C:\Program Files\Schneider Electric\Advantys\Data for a default installation)

If the string value is different from the actual pathname:
  • Double click on the DATA string value to open the String Editor window
  • Change the string to the correct pathname.
  • Click on the OK button to apply the changes and close the String Editor window.
  • Close the Registry Editor .
  • Start the Advantys software.

    WARNING: BE VERY CAREFUL WHEN USING THE REGUSTRY EDITOR. IF THESE STEPS  ARE NOT FOLLOWED EXACTLY, YOU MAY INADVERTENTLY DELETE SOMETHING ELSE WHICH CAN CORRUPT YOUR WINDOWS OPERATING SYSTEM.

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings