How to change the Time and Date on a 174CEV20040 Modbus Plus to Ethernet Bridge?

Issue:

How to change the Time and Date on a 174CEV20040 Modbus Plus to Ethernet Bridge.

Product Line:

174CEV20040 Modbus Plus to Ethernet Bridge

Environment:

Monitor Console Mode (local access to the bridge).

This product was discontinued on 9/24.

Cause:

The 174CEV20040 Modbus Plus to Ethernet Bridge didn’t have the correct time but the user didn’t know how to set it up

Resolution:

To change the Time and Date on a 174CEV20040 bridge, the procedure must be performed using the Monitor Console Mode.

  1. Connect a standard PC keyboard, mouse, and VGA monitor directly to the bridge connectors.
  2. Power on the bridge and access the Monitor Console screen.
    • Initially, all controls are grayed out and the data fields are read‑only.
  3. Under Administrator Account, select Login and enter the administrator password.
    • The default password is password.
    • Once logged in, the controls become active and Login changes to Logout.
  4. In the Troubleshooting Tools section, open the drop‑down menu and scroll to Time and Date, then select Run.
  5. In the Time and Date properties window, update the required values and select OK to save the changes.

Modbus plus
Note: After all changes have been made press the Reboot button for the system to reboot and all changes to take effect.


슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings