170LNT71000 Devicenet Communication Adapter Exec Upgrade to v.1.41

Issue
The purpose of this Resolution is to inform 170LNT71000 Devicenet Communication Adapter users that the Exec has been upgraded to version 1.41.

Product Line
Momentum
170LNT71000

Resolution
Version 1.41 firmware resolves the following 170LNT71000 issues:

1) When operating in 'Polled Mode' and mounted on discrete input bases only, 170LNT71000 Devicenet Comm Adapters would drop off the network every 10 seconds. The adapters would remain off the network for approximately 0.5 second then recover on its own.

2) The input data from a bidirectional module will freeze at their last value if an output fault (ie. shorted output) occurs. The user would have to remove the fault to continue to read inputs correctly.

3) If bi-directional modules are configured for polled & strobe modes, their outputs would remain in their last state if:

    • the communications cable is removed from the adapter,
    • the PLC is stopped, or
    • the fieldbus power is turned off.

The 170LNT71000 firmware is NOT field upgradable

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군

도움이 필요하신가요?

  • 제품 선택기

    애플리케이션에 적합한 제품과 액세서리를 빠르고 쉽게 찾을 수 있습니다.

  • 견적 받기

    영업 관련하여 온라인으로 문의하시면 전문가가 연락드립니다.

  • 구매처

    해당 지역의 가장 가까운 슈나이더 일렉트릭 대리점을 쉽게 찾을 수 있습니다.

  • 지원 센터

    한 곳에서 모든 요구 사항에 대한 지원 리소스를 찾아보십시오.

  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings