브랜드

슈나이더 일렉트릭 코리아 웹사이트에 방문해 주셔서 감사합니다.

슈나이더 일렉트릭 코리아 웹사이트 방문자 분들 모두 환영합니다.
		
오늘 무엇을 도와드릴까요?
What is the best way to start troubleshooting Ethernet devices?

Goals and Symptoms

What is the best way to start troubleshooting Ethernet devices?

Causes and Fixes

If you are having problems communicating to an Ethernet device over a network and you can not ping the module, then connect a cross over cable from a local PC to the device itself. This eliminates any other issues with the network that could be causing the problems. When having a crossed connection to a device and you want to ping it, you must know if your PC and the device that you are trying to connect with are on the same subnet. Being on the same subnet means that if you are using a subnet mask of 255.255.255.0 then for two devices to talk the three first octets in the source IP address and the destination IP need to match. Once you can ping the device then move onto connecting with the device with Concept, ProWorx or Unity..

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings