PM820 Date and Time Can Not be Changed

Issue
Unable to change the date and time of a PM820 meter.

Product
PM820 - Series 800 Power Meter

Environment
PM820
Firmware Version 10.310

Cause
This problem has been identified only on a PM820 with firmware version 10.310.

Resolution

There are 2 possible solutions.
First solution: Upgrade the firmware to version 10.410 or greater.

Access to firmware upgrade instructions can be found here, and a how-to video and a link to the latest firmware
can be found at: How to upgrade firmware on a PM800 series meter from version OS 10.060 or below to the latest version | Schneider Electric USA

Additionally, supporting documents and file downloads on this and a wide variety of other products and topics may be obtained
using the search function found at the: Download Center


Second solution: apply the following procedure:
To change the time, you have to:

1) change "HOUR"
2) press "OK"
3) change "MIN"
4) press "OK"
5) change "SEC"
6) press "OK"
7) change desired time format (24H or AM/PM)
8) DO NOT press "OK"; instead press UP ARROW button (left softkey)

NOTE: If format was changed then UP ARROW again and you will be prompted to save; Else you're done.

To change the date, you have to:

1) change "MONTH"
2) press "OK"
3) change "DAY"
4) press "OK"
5) change "YEAR"
6) press "OK"
7) change desired date format
8) DO NOT press "OK"; instead press UP ARROW button (left softkey)

NOTE: If format was changed then UP ARROW again and you will be prompted to save; Else you're done.

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings