How far away from the Circuit Monitor Series 2000 can I mount the RTM (ride-through module)?
Issue:
Customer would like to mount the RTM physically and needs to know the maximum distance allowed from the CM2000 Series.
Product Line:
CM2150
CM2250
CM2350
CM2450
Environment:
Installation of a Ride-Through Module on a CM2000 Series Meter
Cause:
The RTM was installed in a location that did not comply with the required mounting distance from the Circuit Monitor.
Resolution:
The RTM can be mounted on the back of the Circuit Monitor or can be mounted remotely, as long as it is mounted within 10 feet of the Circuit Monitor.