Energy Meter shows "Phase Loss" Alarm
Issue
Energy meter shows “Phase Loss” alarm on front display.
Product Line
Energy meter (EMB and EME series).
Environment
Installing/wiring energy meter
Cause
If the voltage of any phase is measured as less than 75% of the voltage on any other phase, the display will show PHASE LOSS and indicate the specific phase(s).
Resolution
If the energy meter is installed with the proper number of phases (see selection below to determine this) then the phase voltages should be verified. If the number of phases installed is not correct, then the phase loss alarm will be indicated in all operating conditions.
It’s very important to know the model number of your Energy meter.
For example, users see “Phase Loss” error when they use EMB2043 (1 phase, 3 wire) with 1 phase, 2 wire application.
As a result, it’s very important for users to know their application and use appropriate meter that meets their system type. Please review the tables below for selecting correct meter.
Basic 120/240 Volt 208 Wye
| EMB1010 Basic 100A | 1 Phase, 2 wire installation | 1 CT |
| EMB1021 Basic 200A | 1 Phase, 2 wire installation | 1 CT |
| EMB1032 Basic 300A | 1 Phase, 2 wire installation | 1 CT |
| EMB2010 Basic 100A | 1 Phase, 3 wire installation | 2 CTs |
| EMB2021 Basic 200A | 1 Phase, 3 wire installation | 2 CTs |
| EMB2032 Basic 300A | 1 Phase, 3 wire installation | 2 CTs |
| EMB2043 Basic 400A | 1 Phase, 3 wire installation | 2 CTs |
| EMB2083 Basic 800A | 1 Phase, 3 wire installation | 2 CTs |
| EMB3010 Basic 100A | 3 Phase, 4 wire installation | 3 CTs |
| EMB3021 Basic 200A | 3 Phase, 4 wire installation | 3 CTs |
| EMB3032 Basic 300A | 3 Phase, 4 wire installation | 3 CTs |
| EMB3043 Basic 400A | 3 Phase, 4 wire installation | 3 CTs |
| EMB3083 Basic 800A | 3 Phase, 4 wire installation | 3 CTs |
| EMB3084 Basic 800A | 3 Phase, 4 wire installation | 3 CTs |
| EMB3164 Basic 1600A | 3 Phase, 4 wire installation | 3 CTs |
Extended Range 120/480 Volt Wye
| EME1010 Basic 100A | 1 Phase, 2 wire installation | 1 CT |
| EME1021 Basic 200A | 1 Phase, 2 wire installation | 1 CT |
| EME1032 Basic 300A | 1 Phase, 2 wire installation | 1 CT |
| EME2010 Basic 100A | 1 Phase, 3 wire installation | 2 CTs |
| EME2021 Basic 200A | 1 Phase, 3 wire installation | 2 CTs |
| EME2032 Basic 300A | 1 Phase, 3 wire installation | 2 CTs |
| EME2043 Basic 400A | 1 Phase, 3 wire installation | 2 CTs |
| EME2083 Basic 800A | 1 Phase, 3 wire installation | 2 CTs |
| EME3010 Basic 100A | 3 Phase, 4 wire installation | 3 CTs |
| EME3021 Basic 200A | 3 Phase, 4 wire installation | 3 CTs |
| EME3032 Basic 300A | 3 Phase, 4 wire installation | 3 CTs |
| EME3043 Basic 400A | 3 Phase, 4 wire installation | 3 CTs |
| EME3083 Basic 800A | 3 Phase, 4 wire installation | 3 CTs |
| EME3084 Basic 800A | 3 Phase, 4 wire installation | 3 CTs |
| EME3164 Basic 1600A | 3 Phase, 4 wire installation | 3 CTs |
NOTE: the meter will operate, however the phase loss alarm will constantly be present if the improper meter is in use.
게시 대상: 슈나이더 일렉트릭 Korea







