브랜드

슈나이더 일렉트릭 코리아 웹사이트에 방문해 주셔서 감사합니다.

슈나이더 일렉트릭 코리아 웹사이트 방문자 분들 모두 환영합니다.
		
오늘 무엇을 도와드릴까요?
Power Monitoring Expert : Database Maintenance Task Schedules

Issue

What are the default schedules for the scheduled jobs in Power Monitoring Expert?

Environment
StruxureWare Power Monitoring 7.0.x
Power Monitoring Expert 7.x, 8.x, 9.0, 2020

Resolution

The following Windows Scheduled Tasks are present in SPM systems as of version 7.0.1. The following table shows all the available scheduled task by type of installation and their default execution times.

Task NameSystemSchedule
[ION_Data] - BACKUP - JobSQL ExpressEvery Friday at midnight.
[ION_Network] - BACKUP - JobSQL ExpressDaily at 1:00 AM
[ION_Data] - MAINTENANCE - JobSQL ExpressDaily at 2:00 AM
[ION_Data] - SIZE NOTIFICATION - JobSQL ExpressDaily at 3:00 AM
[ION_Network] - MAINTENANCE - JobSQL ExpressDaily at 7:30 AM
[ION_SystemLog] - TRIM - JobSQL ExpressDaily at 4:00 AM
[ION_SystemLog] - MAINTENANCE - JobSQL ExpressDaily at 7:05 AM
[ApplicationModules] - MAINTENANCE - JobSQL Express and StandardDaily at 3:30 AM
[ApplicationModules] - TRIM - JobSQL Express and StandardDaily at 2:30 AM
[ApplicationModules] - BACKUP - JobSQL Express and StandardDaily at 1:30 AM

FAQ - FA233177 explains "How to modify database maintenance schedules contained in Windows Task Scheduler".

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings