브랜드

슈나이더 일렉트릭 코리아 웹사이트에 방문해 주셔서 감사합니다.

슈나이더 일렉트릭 코리아 웹사이트 방문자 분들 모두 환영합니다.
		
오늘 무엇을 도와드릴까요?
Creating Kernel Dumps for PowerLogic Scada and PowerScada Expert

Steps for getting the kernel dump files:


  • - Make sure you have a User Named Kernel with password kernel in Project Editor with Roles set as ES_Admin.

Citect Project Editor

User

- Open Powerlogic Scada Runtime Manager. Highlight the Process you want to take the kernel dump for, right click on it and select kernel.

Runtime Manager
    • - The kernel window will open as shown below. Then go to tools then click on Reset Stats
Citect Kernel
    • - Then go to View and click on Cicode. Then it will ask you for the password. The password is kernel.
Citect Kernel
    • - After typing the password, a new window will open in which you type in it the function dumpkernel(0xC000,) and click enter. The return value should be 0 as shown below.

Citect Kernel





-After you have done this for all the I/O Servers, Alarm server and trend server your next step will be to copy the created files. You should see a file for each I/O, Alarm and trend Servers


-Navigate to Citect explorer and select View, Log Folder, as shown below: This will take you to the location of the Log Files.

PLS Example

-The files you would need are the ones that are created today with the word Kernel in the beginning of the name and .dat file extension.

Image

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings