Internet Explorer cannot display the webpage" or "The page cannot be displayed" when browsing to the Powerlogic Scada Webclient.

When the user tries to access the webclient on the server he will get the following error:

Internet Explorer cannot display the webpage

OR

The page cannot be displayed

There are no other errors in Windows event viewer.

IE Error
textCause

HTTP Keep-Alives are disabled in Internet Information Services (IIS)


Resolution


"Enable HTTP Keep-Alives" must to be checked in IIS

For IIS6:
1. Open IIS. Start>Control Panel>Administrative Tools>Internet Information Services (IIS) Manager.
2. Expand Web Sites
3. Right-click on Default Web Site (Server operating systems only)
4. Select Properties
5. On the Web Site tab, check "Enable HTTP Keep-Alives"
6. Click Apply and OK
7. Rerun the webclient.
Default Web Settings

For IIS7:
1. Start>Run, type INETMGR, press Enter
2. Click on the Web Site (Default Web Site in our case)
3. In the Features View, double click HTTP Response Headers
4. Click on Set Common Headers… in Actions panel OR Right click in the HTTP Response Headers Feature Page and click Set Common Headers…


HTTP response

5. Check the Enable HTTP Keep-Alive if it is not already enabled.


Set Common HTTP

6. Click OK
7. Rerun the webclient.

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군

도움이 필요하신가요?

도움이 필요하신가요?

제품 선택기

제품 선택기

애플리케이션에 적합한 제품과 액세서리를 빠르고 쉽게 찾을 수 있습니다.

견적 받기

견적 받기

영업 관련하여 온라인으로 문의하시면 전문가가 연락드립니다.

구매처

구매처

해당 지역의 가장 가까운 슈나이더 일렉트릭 대리점을 쉽게 찾을 수 있습니다.

지원 센터

지원 센터

한 곳에서 모든 요구 사항에 대한 지원 리소스를 찾아보십시오.

  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings