Internet Explorer cannot display the webpage" or "The page cannot be displayed" when browsing to the Powerlogic Scada Webclient.

When the user tries to access the webclient on the server he will get the following error:

Internet Explorer cannot display the webpage

OR

The page cannot be displayed

There are no other errors in Windows event viewer.

IE Error
textCause

HTTP Keep-Alives are disabled in Internet Information Services (IIS)


Resolution


"Enable HTTP Keep-Alives" must to be checked in IIS

For IIS6:
1. Open IIS. Start>Control Panel>Administrative Tools>Internet Information Services (IIS) Manager.
2. Expand Web Sites
3. Right-click on Default Web Site (Server operating systems only)
4. Select Properties
5. On the Web Site tab, check "Enable HTTP Keep-Alives"
6. Click Apply and OK
7. Rerun the webclient.