BCPM becomes unresponsive after firmware upgrade to panel 2 (base address +1)

Issue
A BCPM may become unresponsive after an attempt to upgrade the firmware of panel 2 of the device (base address +1). Below is a possible error that may occur after attempting to do so. After the failed upgrade the device may become unresponsive and/or it may not be possible to read data from either panel 1 or panel 2.

Error: "Device Error=516". The error code means the device failed to respond
image

Product Line
Branch Circuit Power Meter (BCPM)
DLF-3000

Environment
Firmware Upgrade

Cause
The BCPM consists of 2 panels (1 and 2). Panel 1 will use the base Modbus address as configured according to the DIP switches. Panel 2 will use the base address +1. Firmware should not be installed to both panels as doing so may cause the device to become unresponsive. Firmware only needs to be installed to the device using it's base address.

Resolution
*Warning: The firmware utilities listed here can cause permanent damage to your product if applied incorrectly. Before downloading any firmware updates, verify the firmware you are downloading is appropriate for the specific model number of your product. If you have any doubts, contact Technical Support for guidance.*

*Warning: Devices should be disconnected from all monitoring software before performing a firmware upgrade*


Do not power down the device. Use the DLF-3000 utility to re-install the firmware to the device using the base address. The BCPM should be able to re-enter the firmware download mode again.

It is important to ensure that BCPMs, in any given system, have an offset of +2. This will ensure that there is no conflict between BCPM A (Panel 1 and 2) and BCPM B (Panel 1 and 2).

Use the following link to download the DLF-3000 software:
DLF-3000 Download

*Refer to Article FA278575 for BCPM firmware upgrade instructions.

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군

도움이 필요하신가요?

도움이 필요하신가요?

제품 선택기

제품 선택기

애플리케이션에 적합한 제품과 액세서리를 빠르고 쉽게 찾을 수 있습니다.

견적 받기

견적 받기

영업 관련하여 온라인으로 문의하시면 전문가가 연락드립니다.

구매처

구매처

해당 지역의 가장 가까운 슈나이더 일렉트릭 대리점을 쉽게 찾을 수 있습니다.

지원 센터

지원 센터

한 곳에서 모든 요구 사항에 대한 지원 리소스를 찾아보십시오.

  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings