브랜드

슈나이더 일렉트릭 코리아 웹사이트에 방문해 주셔서 감사합니다.

슈나이더 일렉트릭 코리아 웹사이트 방문자 분들 모두 환영합니다.
		
오늘 무엇을 도와드릴까요?
Event Timestamps in Management Console Show in UTC Time Instead of Local Time

Issue
Event Timestamps in Management Console are displayed in Coordinated Universal Time (UTC) rather than in local time. Adjusting the server time zone in Windows settings has no effect on the timestamps.

Product Line
ION Enterprise
Power Monitoring Expert (PME) 7.x
Power Monitoring Expert (PME) 8.x
Power Monitoring Expert (PME) 9.x
Power Monitoring Expert (PME) 2020
Power Monitoring Expert (PME) 2021
Power Monitoring Expert (PME) 2022
Power Monitoring Expert (PME) 2023
Power Monitoring Expert (PME) 2024

Environment
Power Monitoring Expert (PME) Management Console

Resolution 1: Older Versions
A timestamp setting in Management Console is not configured correctly.

  1. Open the Event tab under Devices or Sites, whichever is showing UTC time.
  2. Right-click the grey section in the title bar and select Properties.
  3. Select the Row Properties tab from the Option window.
  4. Check the Convert timestamps to local date and time box.
old management console screen

Resolution 2: Newer Versions

  1. Open Managment Console
  2. Click on Tools > Options
  3. Make sure the box for "Convert Timestamps to local date and time" is selected
new options section in management console

All timestamps will now be displayed in the local time zone of the computer running Management Console.

NOTE: This setting is applied to all Event timestamps.

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings